99% Efficient three-phase buck-type SiC MOSFET PFC rectifier minimizing life cycle cost in DC data centers

Research output: Contribution to journalArticleAcademicpeer-review

Abstract

Due to the increasing power consumption of data centers, efficient dc power distribution systems have become an important topic in research and industry over the last years and according standards have been adopted. Furthermore the power consumed by telecommunication equipment and data centers is an economic factor for the equipment operator, which implies that all parts of the distribution system should be designed to minimize the life cycle cost, i.e. the sum of first cost and the cost of the power conversion losses. This paper demonstrates how semiconductor technology, chip area, magnetic component volumes and switching frequency can be selected based on life cycle cost, using analytical and numerical optimizations. A three-phase buck-type PFC rectifier with integrated active filter for 380V dc distribution systems is used as an example system, which shows that a peak efficiency of 99% is technically and economically feasible with state-of-the-art SiC MOSFETs and nanocrystalline or ferrite cores. Measurements taken on an 8 kW, 4 kWdm-3 hardware prototype demonstrate the validity and feasibility of the design.
Original languageEnglish
Article number7947997
Pages (from-to)47-58
Number of pages12
JournalCPSS Transactions on Power Electronics and Applications
Volume2
Issue number1
DOIs
Publication statusPublished - 1 Jan 2017
Externally publishedYes

Keywords

  • Rectifiers
  • Active filters
  • Semiconductor diodes
  • Inductors
  • Capacitors
  • Power electronics
  • MOSFET
  • n/a OA procedure

Fingerprint

Dive into the research topics of '99% Efficient three-phase buck-type SiC MOSFET PFC rectifier minimizing life cycle cost in DC data centers'. Together they form a unique fingerprint.

Cite this