Analysis of harmonic current interaction in an industial plant

Vladimir Cuk, Sjef Cobben, Wil L. Kling, R.B. Timens

    Research output: Chapter in Book/Report/Conference proceedingConference contributionAcademicpeer-review

    32 Downloads (Pure)

    Abstract

    An analysis of current transients caused by the operation of a nearby device in an industrial plant is presented in the paper. The source of current transients in the factory lighting system was traced to the operation of the nearby six-pulse AC/DC converter. To determine the nature of the interaction, a measurement was done with a storage oscilloscope. Also, laboratory experiments on one lamp were conducted. It was possible to exclude the presence of a parallel resonance on this site. It was concluded that transients are caused by voltage notches in certain working regimes of the six-pulse converter. Possible solutions to the problem are separating the supplies of the converter and the lighting installation, filtering, or adding additional line reactance.
    Original languageUndefined
    Title of host publicationProceedings of the 21st International Conference and Exhibition on Electricity Distribution (CIRED2011)
    Place of PublicationFrankfurt am Main
    PublisherCIRED
    Pages1-4
    Number of pages4
    ISBN (Print)2032-9644
    Publication statusPublished - 6 Jun 2011
    Event21st International Conference and Exhibition on Electricity Distribution, CIRED 2011 - Frankfurt am Main, Germany
    Duration: 6 Jun 20119 Jun 2011

    Publication series

    Name
    PublisherCIRED
    ISSN (Print)2032-9644

    Conference

    Conference21st International Conference and Exhibition on Electricity Distribution, CIRED 2011
    Period6/06/119/06/11
    Other6-9 June 2011

    Keywords

    • METIS-278802
    • EWI-20526
    • IR-78060

    Cite this