@inproceedings{b9e4a8ccbffb430bb0acac35f35650e4,
title = "Analysis of harmonic current interaction in an industial plant",
abstract = "An analysis of current transients caused by the operation of a nearby device in an industrial plant is presented in the paper. The source of current transients in the factory lighting system was traced to the operation of the nearby six-pulse AC/DC converter. To determine the nature of the interaction, a measurement was done with a storage oscilloscope. Also, laboratory experiments on one lamp were conducted. It was possible to exclude the presence of a parallel resonance on this site. It was concluded that transients are caused by voltage notches in certain working regimes of the six-pulse converter. Possible solutions to the problem are separating the supplies of the converter and the lighting installation, filtering, or adding additional line reactance.",
keywords = "METIS-278802, EWI-20526, IR-78060",
author = "Vladimir Cuk and Sjef Cobben and Kling, {Wil L.} and R.B. Timens",
note = "eemcs-eprint-20526 ",
year = "2011",
month = jun,
day = "6",
language = "Undefined",
isbn = "2032-9644",
publisher = "CIRED",
pages = "1--4",
booktitle = "Proceedings of the 21st International Conference and Exhibition on Electricity Distribution (CIRED2011)",
}