Design and testing of a setup for on-site power measurements in high-voltage grids

  • Gert Rietveld
  • , Martin Fransen
  • , Nicolas V.F. Blanc
  • , Eddy So

Research output: Chapter in Book/Report/Conference proceedingConference contributionAcademicpeer-review

Abstract

A three-phase reference system for in-situ calibration of High Voltage (HV) Revenue Metering Systems in substations has been established. It consists of a high-accuracy three-phase power meter, including corresponding current and voltage transformers (CTs and VTs). The reference system is capable of performing power measurements up to 150 kV system voltage and line currents up to 5000 A. The excellent results of the calibration and further testing of power meter, CTs, and VTs indicate that an overall system uncertainty of better than 100μW/VA can be achieved.

Original languageEnglish
Title of host publicationAMPS 2019 - 2019 10th IEEE International Workshop on Applied Measurements for Power Systems, Proceedings
Place of PublicationPiscataway, NJ
PublisherIEEE
ISBN (Electronic)978-1-7281-0075-3
ISBN (Print)978-1-7281-0076-0
DOIs
Publication statusPublished - Sept 2019
Externally publishedYes
Event10th IEEE International Workshop on Applied Measurements for Power Systems, AMPS 2019 - Aachen, Germany
Duration: 25 Sept 201927 Sept 2019
Conference number: 10

Publication series

NameAMPS - IEEE International Workshop on Applied Measurements for Power Systems, Proceedings
PublisherIEEE
Number10
Volume2019
ISSN (Print)2473-1315
ISSN (Electronic)2475-2304

Conference

Conference10th IEEE International Workshop on Applied Measurements for Power Systems, AMPS 2019
Abbreviated titleAMPS 2019
Country/TerritoryGermany
CityAachen
Period25/09/1927/09/19

Keywords

  • Billing
  • Calibration
  • Current transformer
  • High current
  • High voltage (HV)
  • Power
  • Power meter
  • Precision measurements
  • Revenue metering
  • Substation
  • Voltage transformer

Fingerprint

Dive into the research topics of 'Design and testing of a setup for on-site power measurements in high-voltage grids'. Together they form a unique fingerprint.

Cite this