Skip to main navigation Skip to search Skip to main content

Feasibility of direct measurement of HVDC converter station loss

  • A. Bergman
  • , G. Rietveld

Research output: Contribution to journalArticleAcademicpeer-review

119 Downloads (Pure)

Abstract

Losses of HVDC converter stations need to be accurately quantified to support evaluation of bids for such systems and to underpin efforts to reduce greenhouse gas emissions. At present, these losses are estimated, based on loss calculations for individual converter components, and no reliable method exists to measure the actual HVDC converter station loss as difference between power on the AC-and DC-side of the station. The necessary requirements for such a measurement are investigated in this study, and a tentative design of a suitable loss measuring setup is explored. This approach is a useful alternative for those cases where a direct measurement of losses via a temporary connection with two converters operating in back-to-back mode cannot be made.

Original languageEnglish
Pages (from-to)85-93
Number of pages9
JournalCIGRE Science and Engineering
Volume15
Publication statusPublished - 2019
Externally publishedYes

UN SDGs

This output contributes to the following UN Sustainable Development Goals (SDGs)

  1. SDG 7 - Affordable and Clean Energy
    SDG 7 Affordable and Clean Energy
  2. SDG 13 - Climate Action
    SDG 13 Climate Action

Fingerprint

Dive into the research topics of 'Feasibility of direct measurement of HVDC converter station loss'. Together they form a unique fingerprint.

Cite this