Performance evaluation of air-source heat pump based on a pressure drop embedded model

Tim Koopman, Tingting Zhu*, Wilko Rohlfs

*Corresponding author for this work

Research output: Contribution to journalArticleAcademicpeer-review

3 Citations (Scopus)
24 Downloads (Pure)

Abstract

An air-source heat pump simulation model, accounting for evaporator and condenser pressure drop, has been developed. The model is capable of computing the heat pump’s coefficient of performance (COP) under different ambient temperatures and relative humidities above frosting conditions. This research extends an existing iterative simulation method that relies on the equalization of logarithmic mean temperature differences (LMTDs) calculated through two different approaches by adding a pressure drop simulation. Frictional and acceleration pressure drop is considered, computed iteratively. Simulation results for three different refrigerants, R410A, R32 and R290, are compared. The model’s accuracy is validated by comparing simulated COP values with measured COP values from the reference heat pump datasheet. The model closely replicates the measured COP values above frosting conditions, with only a slight under-estimation of approximately 1.5%. Results show a substantial impact of ambient temperature on the COP. For instance, an ambient temperature of 20 ◦C, compared to 7 ◦C, results in a COP increase of up to 35%, while an ambient temperature of − 10 ◦C leads to a 26% reduction in COP. Relative humidity enhances the COP if air moisture condensation becomes possible. Higher condenser capacities negatively affect the COP. The study highlights the differences in pressure drop characteristics between the condenser and the evaporator for the modeled heat pump, with maximum pressure drops of 220 kPa and 50 kPa for the condenser and evaporator, respectively. Additionally, the choice of refrigerant significantly influences pressure drop, with R32 displaying
the lowest pressure drop, R410A showing the highest condenser pressure drop, and R290 causing the highest evaporator pressure drop.
Original languageEnglish
Article numbere24634
Number of pages21
JournalHeliyon
Volume10
Issue number4
Early online date9 Feb 2024
DOIs
Publication statusPublished - 29 Feb 2024

Keywords

  • UT-Gold-D

Fingerprint

Dive into the research topics of 'Performance evaluation of air-source heat pump based on a pressure drop embedded model'. Together they form a unique fingerprint.

Cite this