Skip to main navigation Skip to search Skip to main content

Voltage Dependence of the Reference System in Medium-and High-Voltage Current Transformer Calibrations

  • Helko E. van den Brom*
  • , Ronald van Leeuwen
  • , Gert Rietveld
  • , Ernest Houtzager
  • *Corresponding author for this work

Research output: Contribution to journalArticleAcademicpeer-review

7 Downloads (Pure)

Abstract

A sampling current ratio measurement system has been developed to calibrate the voltage dependence of ratio error and phase displacement of current transformers (CTs) used for medium-voltage (MV) and high-voltage (HV) applications. The influence of voltage-induced leakage current on the apparent ratio error and phase displacement of the reference circuit was unambiguously demonstrated using a novel measurement method. Measurement results for voltages up to 24 kV show that the observed leakage current is purely capacitive and caused by the shielded cable capacitance of the HV cable used to feed the current. The maximum ratio error and phase displacement were found to be about 100 parts in 106 and 100~\mu rad for the smallest current of 100 A used for these investigations. Since these values scale linearly with the applied voltage and inversely proportional with current, the assumption of negligible voltage dependence used in other reference systems presented in literature is questionable. Using the corrected reference circuit, a commercial class 0.2S MV CT with 2500-A nominal current was calibrated at voltage levels up to 24 kV. The voltage dependence of ratio error and phase displacement for primary currents up to 500 A was demonstrated to be capacitive as well, with a maximum impact on the current ratio of almost 0.9% for a primary current of 100 A (corresponding to 3.6% at 1% of nominal current). This value is beyond the limits of in-force standards, which emphasizes the necessity of implementing voltage dependence testing in those standards.

Original languageEnglish
Article number9380167
JournalIEEE transactions on instrumentation and measurement
Volume70
Early online date17 Mar 2021
DOIs
Publication statusPublished - 2021
Externally publishedYes

Keywords

  • Current measurement
  • Current transformers (CTs)
  • High voltage (HV)
  • Measurement standards
  • Phase displacement
  • Precision measurements
  • Ratio error
  • Voltage dependence

Fingerprint

Dive into the research topics of 'Voltage Dependence of the Reference System in Medium-and High-Voltage Current Transformer Calibrations'. Together they form a unique fingerprint.

Cite this